PolyComp Serial Interface cards - Dip Switch Settings
The RS232 or RS485 interface card has a number of dip switch settings.


There are two banks of dip switches, a bank of 8 dip switches and a bank of 6 dip switches.

Bank 1 setting

Protocol Settings
Switch Position Description ON OFF
Switch 1 Stop Bits 1 Stop Bit 2 Stop Bits
Switch 2 Parity Set Even Parity Odd Parity
Switch 3 Data Bits 7 Data Bits 8 Data Bits
Switch 4 Parity Enable YES – Parity Enabled NO – Parity Disabled
Switch 5 Not Used Not Used Not Used
Baud Rate Settings
Baud Rate
Switch 6 Position
Switch 7 Position
Switch 8 Position
1200 OFF OFF OFF
600 OFF OFF ON
1200 OFF ON OFF
2400 OFF ON ON
4800 ON OFF OFF
9600 ON OFF ON
19200 ON ON OFF
19200 ON ON ON

Bank 2 setting

Address Settings – 1 = ON, 0 = OFF
Add
No.
1
2
3
4
5
6
Add
No.
1
2
3
4
1
0
0
0
0
0
1
17
0
1
0
0
0
1
2
0
0
0
0
1
0
18
0
1
0
0
1
0
3
0
0
0
0
1
1
19
0
1
0
0
1
1
4
0
0
0
1
0
0
20
0
1
0
1
0
0
5
0
0
0
1
0
1
21
0
1
0
1
0
1
6
0
0
0
1
1
0
22
0
1
0
1
1
0
7
0
0
0
1
1
1
23
0
1
0
1
1
1
8
0
0
1
0
0
0
24
0
1
1
0
0
0
9
0
0
1
0
0
1
25
0
1
1
0
0
1
10
0
0
1
0
1
0
26
0
1
1
0
1
0
11
0
0
1
0
1
1
27
0
1
1
0
1
1
12
0
0
1
1
0
0
28
0
1
1
1
0
0
13
0
0
1
1
0
1
29
0
1
1
1
0
1
14
0
0
1
1
1
0
30
0
1
1
1
1
0
15
0
0
1
1
1
1
31
0
1
1
1
1
1
16
0
1
0
0
0
0
32
1
0
0
0
0
0
Copyright © 2007 PolyComp (Pty) Ltd. All Rights Reserved.
STANDARDS: CISPR 55, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11, EMC-EN50082-1, SAFETY-IEC950 AND EN60950
Click to view vacancies at PolyComp